AVC Motor Drive
Actuator AVC RS - two-point

Actuator AVC RS - two-point

The AVC R actuator is used to switch between different heat sources or to switch between space heating and domestic hot water heating.

Use

  • For controlling various mixing valves in heating and cooling systems, as well as in ventilation systems.
  • Switch between heating and cooling.
  • Switch between heating and domestic hot water.
  • Switch between different heat sources.
  • In solar systems.
  • In domestic hot water systems.
  • As a component in central heating installations.

Key features of the AVC actuator

  • Can be mounted directly on more than 20 different mixing valves.
  • Robust construction.
  • Four possible installation positions.
  • Engine protection in the event of a mixing valve blockage.
  • LED operation signalling.
  • It can be fitted to rotary mixing and ball valves.
  • It is used to control the mixing heating branches.
COMPARISON OF THE PERFORMANCE OF ACTUATORSAVCAVCSAVCRAVCRSAVCY
USE
For controlling mixing valves in heating or cooling systemsYesYesNoNoNo
Switching between heating and coolingNoNoYesYesNo
Switching between heating and domestic water heatingNoNoYesYesNo
Switching between different heat sources NoNoYesYesNo
In solar systemsNoNoYesYesNo
In domestic hot water heating systemsYesYesYesYesNo
Regulates elements of ventilation systemsNoNoNoNoYes
Miscellaneous other central heating appliancesYesYesYesYesYes
THE MOMENT OF RETURN
5 NmYesYesYesYesNo
10 NmYesYesYesYesYes
15 NmYesYesYesYesYes
MODE OF OPERATION
Two-pointNoNoYesYesNo
Three pointsYesYesNoNoNo
Proportionate NoNoNoNoYes
PUMP SWITCH OFF
Adjustable auxiliary switch to switch the circulation pump on/off in any positionNoYesNoYesNo
POSSIBLE ROTATION SPEEDS
15 sec / 90° YesYesNoNoYes
30 sec / 90° YesYesYesYesYes
60 s / 90°YesYesYesYesYes
120 s / 90°YesYesYesYesYes
240 s / 90°YesYesYesYesNo
480 s / 90°YesYesYesYesYes
ADVERTISING
230 V ~, 50 Hz YesYesYesYesNo
24 V ~, 50 Hz YesYesYesYesNo
24 V~ / 24 V=NoNoNoNoYes
POSSIBLE VERSIONS OF THE MANUAL LEVER
ButtonYesYesYesYesYes
RočicaYesYesYesYesYes
Valve position indicator onlyYesYesYesYesYes
SAFETY
Engine protection in case of mixing valve blockageYesYesYesYesYes
DEMONSTRATION OF OPERATION
LED display of the direction of rotation of the mixing valveYesYesYesYesYes
Technical dataAVC RS
Connection voltage230 VAC or 24 VAC
Own consumption< 5 W
Additional switch to switch off the pump230 VAC, 3 A
Degree of protectionIP42
Safety classII for 230 VAC voltage III for 24 V~ voltage
Housing materialPC - dark grey
Standard cable length2 m
Operating temperature0÷50 °C
Storage temperature-20÷75 °C
Product weight390÷860 g
Number of pieces per packing unit24 pieces
Actuator dimensions with knob
Actuator dimensions with knob

Dimensions of actuator with crank
Dimensions of actuator with crank

Actuator dimensions with indicator
Actuator dimensions with indicator

Electrical connection
Electrical connection of the AVCRS motor drive

Lead Form Test
Step 1 of 5

WANT ADVICE OR A QUOTE?

Here you can ask questions about heating and cooling products or make an enquiry for your project. If you already have technical documents, plans or additional information about your project, you will be able to add them in later steps.

NOTICE

The Seltron service will be closed from 27 December to 29 December 2023.
Any emergencies or issues that arise during our absence will be dealt with as soon as the service reopens on 3 January 2024.
Thank you for your understanding.

Opening hours of the Seltron store on 30 December 2023.
  • from 7.00 to 12.00